Lennox gas furnace code E310: meaning and exact next steps

E310 means Discharge temperature sensor failure, shown only if the sensor is shorted or out of range. In communicating mode it clears 30 seconds after the fault recovers; in non-communicating mode it clears after the current heat call. This answer applies only to Lennox gas furnaces that use the 103130-XX integrated ignition control, as documented in the Lennox service literature for the Elite EL296UHV(X). Codes appear as E followed by three digits on the control or on the thermostat. Other Lennox controls have their own tables.

On the covered Lennox gas furnace, E310 means discharge temperature sensor failure, shown only if the sensor is shorted or out of range. In communicating mode it clears 30 seconds after the fault recovers; in non-communicating mode it clears after the current heat call. First, look for a damaged or disconnected sensor wire.

Differential

Likely causes of “Lennox gas furnace code E310”, and how to tell them apart

  1. 1

    A shorted or out-of-range discharge temperature sensor

    What separates it E310 shows

    How to confirm Lennox says to compare its resistance with the chart

  2. 2

    A damaged or disconnected sensor wire

    What separates it The code appears after work

    How to confirm Look for a loose or damaged wire

  3. 3

    A failed sensor

    What separates it The reading never changes

    How to confirm Replace the sensor if necessary

  4. 4

    A control fault

    What separates it The sensor tests well

    How to confirm Technician replacement

  5. 5

    A recovered fault

    What separates it The code clears after the fault recovers

    How to confirm Watch the next cycles

Before you touch a setting

Record this first — changing settings destroys the evidence

  • Whether the furnace is communicating with the thermostat
  • How the code clears after a call for heat
  • Any signs of damaged wire near the sensor
  • The furnace model from the label

Try in this order

0 of 8 completed
  1. What to do first

    Reversible

    Look for a damaged or disconnected sensor wire.

  2. Correct only the documented fault domain

    Reversible

    Lennox says to compare the sensor's resistance with the temperature-resistance charts in the installation instructions and replace the sensor if necessary.

  3. Turn the power off

    Reversible

    At the switch.

  4. Look for a damaged wire

    Reversible

    Near the sensor, without touching.

  5. Restart

    Reversible

    And watch the display.

  6. Note whether it clears

    Reversible

    Lennox says 30 seconds after recovery in communicating mode.

  7. Record the pattern

    Reversible

    And time.

  8. Call a technician

    Reversible

    To test the sensor.

Model-specific

What is true of this model and not of its siblings

The discharge sensor
The sensor measures the temperature of the air leaving the furnace, which the control uses to modulate the heat.
Lennox's wording
Shown only if the sensor is shorted or out of range.
Communicating and non-communicating
In communicating mode it clears 30 seconds after recovery; in non-communicating mode it clears after the current heat call.
The test
Lennox says to compare resistance with the temperature-resistance charts.
The wire
Look for a damaged wire, without touching.
Replacement
If the sensor is bad, replace it.
What a sensor reading means
A thermistor changes its electrical resistance with temperature. The control reads the resistance and converts it to a temperature. If the reading is zero, as in a short, or infinite, as in a break, it is out of range, and the control reports E310.
A short or a break
A wire rubbed through by vibration can short, and a wire pulled out of its connector can break. Both look alike to the control. A technician inspects the harness and the connector pins, with the power off.
Clearing the code
Lennox says that in communicating mode the code clears 30 seconds after the fault recovers, and in non-communicating mode it clears after the current heat call. If it clears and returns, the connection is likely intermittent, which a careful inspection often finds.

Stop boundary

When this stops being a self-service repair

  • !Do not touch electrical parts with the power on
  • !Call a qualified technician for a sensor test
  • !Never bypass a sensor
  • !Sensor work is for a technician
  • !Contact Lennox service if the reading stays out of range after wiring is checked

Evidence ledger

Sources behind this answer

Exact questions

Common questions

What does E310 mean on a Lennox gas furnace?+

Discharge temperature sensor failure, shown only if the sensor is shorted or out of range. In communicating mode it clears 30 seconds after the fault recovers; in non-communicating mode it clears after the current heat call.

When does it clear?+

In communicating mode, 30 seconds after the fault recovers.

Is the furnace safe to use?+

Follow the technician's advice.

How is it tested?+

By resistance against a chart.

Where is the discharge sensor?+

In the supply airstream after the heat exchanger, wired back to the control.

Can a bad sensor overheat the furnace?+

The limit switches still guard the heat exchanger; the sensor is used for control.

Wrong device or version?

Match the path before repeating the steps.

Match another device