Goodman gas furnace · exact code

Goodman gas furnace code EE9: meaning and exact next steps

EE9 means The high-stage pressure switch circuit is not closed. The furnace fails to operate on high stage, runs normally on low stage, and the induced-draft blower operates. This answer applies only to Goodman GM9C96/GC9C96 and Amana AM9C96/AC9C96 two-stage furnaces with a nine-speed ECM motor, as documented in Goodman's service and troubleshooting manual RS6612020R1. The furnace shows its fault on a seven-segment display, and the codes here are written as that manual prints them. Other Goodman, Amana or Daikin boards can use a different list.

On the covered Goodman gas furnace, EE9 means the high-stage pressure switch circuit is not closed. The furnace fails to operate on high stage, runs normally on low stage, and the induced-draft blower operates. First, look for anything blocking the flue and inlet air pipes outside, such as snow, ice, leaves or a nest.

Differential

Likely causes of “Goodman gas furnace code EE9”, and how to tell them apart

  1. 1

    A blocked flue or inlet air pipe

    What separates it The furnace runs on low stage but fails on high; common after snow, ice or a nest

    How to confirm Look outside at both pipe terminations

  2. 2

    A cracked, loose or water-filled pressure hose

    What separates it The hose looks collapsed or holds moisture

    How to confirm Inspect the hose for cracks and for a low spot that holds condensate

  3. 3

    An inducer that does not reach high speed

    What separates it The inducer sounds the same on both stages

    How to confirm A technician measures the pressure and the inducer's high-speed performance

  4. 4

    Condensate trapped in the switch hose

    What separates it A hose that sags between the inducer housing and the switch holds a plug of water that keeps the high-stage switch from seeing pressure

    How to confirm With power off, a technician lifts the hose off and blows through it; it should pass air freely

Before you touch a setting

Record this first — changing settings destroys the evidence

  • Whether low stage heats normally
  • What the weather has done recently at the pipe ends
  • Whether the hose is damp or loose
  • The model number from the furnace label

Try in this order

0 of 5 completed
  1. What to do first

    Reversible

    Look for anything blocking the flue and inlet air pipes outside, such as snow, ice, leaves or a nest.

  2. Correct only the documented fault domain

    Reversible

    Goodman's corrective actions: inspect the pressure-switch hose and repair or replace it, inspect the flue and inlet air piping for blockage, proper length, elbows and termination, check induced-draft blower performance and correct as necessary, and tighten or correct the wiring connection.

  3. Go outside and look at both pipes

    Reversible

    Clear snow, ice, leaves or a nest from the flue and the inlet air termination, keeping clear of exhaust gas.

  4. Check the hose

    Reversible

    With the furnace off, look at the pressure-switch hose and replace it if it is cracked, loose or holds water.

  5. Let a technician test the inducer

    Reversible

    Goodman's corrective actions include checking the induced-draft blower's performance and the wiring connection at the switch.

Model-specific

What is true of this model and not of its siblings

Shown as
EE9 on the control board display.
Applies to
Goodman two-stage furnaces with a high-stage pressure switch.

Stop boundary

When this stops being a self-service repair

  • !Do not jumper the high-stage switch
  • !Call a technician for the inducer, hose and switch checks

Evidence ledger

Sources behind this answer

Exact questions

Common questions

What does EE9 mean on a Goodman gas furnace?+

The high-stage pressure switch circuit is not closed. The furnace fails to operate on high stage, runs normally on low stage, and the induced-draft blower operates.

Why does the furnace still heat?+

On this code it runs on low stage normally; only the high stage cannot prove its pressure switch.

Is it safe to keep using low stage?+

It may work, but the fault is still in the draft path. Have it checked before the next cold spell.

Can ice cause EE9?+

Yes. Ice on the pipe end, or a hose with condensate, can keep the switch from closing.

Does low stage running mean the vent is fine?+

Not necessarily. The high stage needs more draft, so a partly blocked pipe can pass the low-stage test and fail the high-stage one.

How soon should it be fixed?+

Before sustained cold weather, because the furnace will lean on its low stage for every call and may not keep up on the coldest days.