Kohler standby generator error codes
Kohler standby generator codes as Kohler Power lists them, each with its meaning and the first safe check.
- AC Sens LossGenerator AC output sensing was lost. Kohler classes
- Accy PwrOver WarningWarning. Accessory power overload — an overcurrent (short-circuit)
- ATS ComErrorWarning. ATS communication error — the transfer-switch interface
Kohler standby generator code Advanced Diagnostic: meaning and exact next steps
Advanced Diagnostic means Shutdown during the reduced-speed portion of an exercise. The engine then restarts, runs at full speed for two minutes and stops; the controller returns to AUTO and the exercise schedule is unchanged.
Open record Kohler standby generator · exact codeKohler standby generator code ATS PhaseRot: meaning and exact next steps
ATS PhaseRot means Warning. Transfer-switch phase rotation does not match, so the ATS will not transfer.
Open record Kohler standby generator · exact codeKohler standby generator code Engine Speed High: meaning and exact next steps
Engine Speed High means Shutdown. Engine speed exceeded 115% of normal running speed for more than 0.3 seconds.
Open record Kohler standby generator · exact codeKohler standby generator code Engine Speed Low: meaning and exact next steps
Engine Speed Low means Shutdown. Engine speed dropped below 85% of normal running speed for more than 3 seconds.
Open record Kohler standby generator · exact codeKohler standby generator code Lo Crank Vlt: meaning and exact next steps
Lo Crank Vlt means Warning. Low cranking voltage — battery voltage dropped below 3.5 VDC during engine cranking.
Open record Kohler standby generator · exact codeKohler standby generator code MainPwrOverL: meaning and exact next steps
MainPwrOverL means Shutdown. Main power overload — an overcurrent (short-circuit) fault on the controller output.
Open record Kohler standby generator · exact codeKohler standby generator code Not in Auto: meaning and exact next steps
Not in Auto means Warning. The generator set is not in AUTO (standby) mode, so remote start and stop commands from a transfer switch or remote switch are ignored.
Open record Kohler standby generator · exact codeKohler standby generator code Spd Sens Flt: meaning and exact next steps
Spd Sens Flt means Shutdown. The engine speed sensor has failed, or the engine stalled.
Open recordEvery code
Every Kohler standby generator code: what it means and what to do
- AC Sens Loss
- Accy PwrOver Warning
- ATS ComError
- Aux Input
- Batt Chg Flt
- Battery CrLo Warning
- Battery Voltage High
- Battery Voltage Low
- Exer Not Sch
- Frequency High
- Frequency Low
- Locked Rotor
- Low Oil Level or Oil Pressure
- Over Crank
- Volts L1-L2 High
- Volts L1-L2 Low
Kohler standby generator code AC Sens Loss
Generator AC output sensing was lost. Kohler classes it a warning after 1 second when no output is detected after crank disconnect, and a shutdown after 3 seconds when voltage was present and then lost. Detection begins 10 seconds after crank disconnect.
Record whether the set was in AUTO and whether it had been producing output.
Contact an authorized dealer for service.
Kohler standby generator code Accy PwrOver Warning
Warning. Accessory power overload — an overcurrent (short-circuit) fault on the accessory controller power output.
Note any accessories wired to the controller accessory output.
Contact an authorized dealer for service.
Kohler standby generator code ATS ComError
Warning. ATS communication error — the transfer-switch interface connection was lost.
Confirm whether the transfer switch still operates.
Kohler directs checking communication wiring between the transfer-switch interface board and the generator set.
Kohler standby generator code Aux Input
Shutdown. An optional customer-connected auxiliary input is closed (digital input from an optional PIM).
Identify which customer-supplied equipment is wired to the auxiliary input.
Check the customer-supplied equipment.
Kohler standby generator code Batt Chg Flt
Warning. Battery charger fault reported to the PIM from an external battery charger — not the controller's built-in charger.
Identify whether an external charger is installed.
Check the external battery charger.
Kohler standby generator code Battery CrLo Warning
Warning. Engine starting battery voltage fell below 11 VDC for more than 10 seconds. Inhibited during cranking; clears when voltage returns to an acceptable level.
Record how old the battery is and whether the set has been exercising.
Kohler directs checking the battery rating and condition, checking battery-charger operation, and charging or replacing the battery.
Kohler standby generator code Battery Voltage High
Warning. Engine starting battery voltage rose above 16 VDC for more than 10 seconds.
Note whether an external charger is connected.
Kohler directs checking the battery rating and condition and checking battery-charger operation.
Kohler standby generator code Battery Voltage Low
Warning. Engine starting battery voltage fell below 12.5 VDC for more than 90 seconds while the engine was not running.
Note whether utility power to the charger has been interrupted.
Kohler directs checking the battery rating and condition, checking battery-charger operation, and charging or replacing the battery.
Kohler standby generator code Exer Not Sch
Warning. No exercise is scheduled on the controller.
Confirm the set has been running its monthly exercise.
Set the exerciser using the procedure in the model's operation manual.
Kohler standby generator code Frequency High
Shutdown. Governed frequency exceeded 110% of the system frequency setpoint for more than 10 seconds. The check becomes active 10 seconds after engine start.
Record the displayed frequency if the controller shows it.
Contact an authorized dealer for service.
Kohler standby generator code Frequency Low
Shutdown. Governed frequency fell below 90% of the system setting for more than 10 seconds, or 1 Hz below it for more than 60 seconds.
Note the connected load at the time of shutdown.
Kohler directs reducing the load and restarting, checking the enclosure thermostat and resetting if tripped, then contacting an authorized dealer.
Kohler standby generator code Locked Rotor
Shutdown. No engine rotation was sensed during cranking; the set shuts down 3 seconds after detection.
Leave the fault displayed and note any cranking sound.
Kohler directs checking the battery and loose connections, then contacting an authorized dealer.
Kohler standby generator code Low Oil Level or Oil Pressure
Shutdown. The low-oil-pressure switch indicated low pressure for more than 5 seconds, or on the 26RCA the oil-level switch indicated low oil. Kohler states plainly that the low-oil-pressure shutdown does NOT protect against low oil level.
Allow the engine to cool, then check the oil level using the procedure in the model's manual.
Kohler directs checking for lubrication-system leaks, checking oil level and adding oil if low, and checking the switch and wiring. If the fault persists, Kohler says do not run the generator set and contact an authorized dealer.
Kohler standby generator code Over Crank
Shutdown. The controller made three unsuccessful starting attempts.
Record whether the fault happened during an outage or a scheduled exercise.
Kohler directs checking the fuel supply, spark plug, battery and loose connections, then contacting an authorized dealer.
Kohler standby generator code Volts L1-L2 High
Shutdown. Generator output voltage exceeded 120% of nominal system voltage for more than 2 seconds.
Do not reconnect sensitive equipment until the cause is identified.
Contact an authorized dealer for service.
Kohler standby generator code Volts L1-L2 Low
Shutdown. Generator output voltage fell below 80% of nominal system voltage for more than 10 seconds.
Note the connected load at the time of shutdown.
Kohler directs reducing the load and restarting, checking the enclosure thermostat and resetting if tripped, then contacting an authorized dealer.
Kohler Power — TP-7092 Operation Manual — Figure 25, Controller Fault Messages